LIST PRICE $5,295.00

23,500 BTU (2-Ton)

General Details
The Model KCW2421 (nominal 2-ton or 23,500 BTU) is the smallest water-cooled unit possible in size and capacity in The Ceiling Master Series, KwiKool’s Line of Above-Ceiling Mounted units. The KCW is a uniquely made product designed to work when other commercially available products wont accomplish the requirements of your application. The Ceiling Master Series, KCW water-cooled models, perform and out last the competition with its small size, high efficiency, and lower cost.

The built-in mounting supports on the unit’s base allow for easy installation by a qualified mechanical contractor above a drop ceiling, using standard, off-the-shelf hardware. All Ceiling Master Series KCW water-cooled above-ceiling mounted units require access to a circulating water system, such as a chilled water system. Using tap water for water-cooled models is not recommended. The KCW models are equipped with a self-regulating internal water regulating valve, which is rated up to 150 psi. KwiKool’s self-contained design also eliminates the need for refrigerant connections, further reducing installation costs. All Ceiling Master Series KCW units come with two mounted flanges, which allow duct connection for the cold air supply and return. The KCW2421 runs on a standard 230-volt/20-amp circuit and uses any 20-volt thermostat. The unit also comes with an internal high lift condensate pump.

And, KwiKool products are proudly MADE IN AMERICA.

made-in-usa-badge

Cooling Capacity (BTUH)
23,500 BTU (2-Ton)
Power Supply
230V / 20 Amp Circuit
Dimensions (WxDxH)
24 x 30 x 20
Specifications
COOLING CAPACITY
BTU/hr @ 95F at 60% RH23,500 (2-Ton)
COMPRESSOR DATA
Compressor TypeHermetic Recip.
Operating Temperatures60-95 F 50%RH
Refrigerant407C
FAN DATA
Evaporator
Fan Type (Centrifugal)Direct Drive
Air Flow (CFM)850
Cold Air Supply10" Collar
Cold Air Return16" Collar
WATER FLOW DATA
Flow ControlAutomatic Pressure Regulating Valve
Inlet Water 85F-95F Exit (GPM)6
Inlet Water 75F-95F Exit (GPM)3
Inlet Water 65F-95F Exit (GPM)2
Inlet Water 55F-95F Exit (GPM)1.5
ELECTRICAL DATA
Power Supply (Volts) 208/230 Single Phase
Current Consumption (Amps) 8.3/7.6
Power Consumption (kW) 1.57
Maximum Circuit Breaker (Amps) 20
Recommended Breaker Size20
Minimum Circuit Ampacity(Amps) 10.75
Min./Max. Voltage 195-225/210-250
DIMENSIONAL DATA
Width x Depth x Height (Inches) 24" x 30" x 20"
Weight (Lbs.) 194
Shipping Weight (Lbs.) 244
SAFETY DEVICE DATA
Compressor Overload Internal
Fan Motor Overload Automatic Internal
Evaporator Freeze Protection Hot Gas Bypass
High Pressure Switch Manual
Low Pressure Switch Automatic
Compressor Short Cycle Yes
Automatic Restart Yes
Thermostat Type Customer supplied
Condensate Pump Overflow Yes
Condensate Pump TypeInternal High lift 20' of head
Fire Alarm Control Safety ShutoffYes
Alarm Output for Building AutomationYes
Detail Drawings
KCW2421DD
Features
  • MADE IN USA
  • 23,500 BTU/H – 2-ton capacity air cooled
  • Compact yet Powerful
  • Runs on 230V 20 amp circuit
  • High Sensible Cooling – Ideal for Server Room Applications
  • All Direct Drive Blowers for Maintenance Free Use
  • THD Technology – Twin Direct Hyper Drives (Some Models)
  • High Static Cold Air Blower for up to 4 ducts for Cold Air Distribution to Hot Spots
  • Works with Almost All Thermostats
  • Signal Output Connects to Building Control System
  • Works with fire alarm Control for Safety Shut Off
  • Internal High Pressure 20-ft. Lift Condensate Pump with Overflow Cutoff
  • Automatic Low Pressure Switch
  • Manual High Pressure Switch
  • Hot Gas Bypass for Freeze Protection
  • Easy Access Service Ports
  • Compressor Short Cycle Protection
  • Automatic Fan Overload Protection
  • Non-CFC Refrigerants
  • Available in Air-Cooled & Water-Cooled Models